Selection of low-voltage electrical components [Essence]

General principles for the selection of low-voltage electrical appliances:

1. The rated voltage of the low-voltage electrical appliance should not be less than the working voltage of the circuit, ie Ue≥Ug.

2. The rated current of the low-voltage electrical appliance should not be less than the calculated working current of the loop, ie Ie≥Ig.

3. The breaking current of the equipment should not be less than the short-circuit current, ie Izh≥Ich

4. The thermal stability guarantee value should not be less than the calculated value.

5. Select low-voltage electrical equipment according to the starting condition of the circuit. For example, the fuse and the automatic air switch need to be selected according to the starting condition.

First, the selection of circuit breakers

Protection: overload, short circuit, under voltage

General selection:

1. The rated voltage of the circuit breaker ≥ the rated voltage of the line;

2. The rated current of the circuit breaker ≥ the line calculates the load current;

3. The rated current of the circuit breaker release ≥ the line calculates the load current;

4, the circuit breaker limit on-off capacity ≥ the maximum short-circuit current in the line;

5. The automatic switching instant (or short delay) tripping setting current of the single-circuit short-circuit current at the end of the line is not less than 1.25 times;

6. The rated voltage of the circuit breaker undervoltage release is equal to the rated voltage of the line.

Selection of power distribution circuit breakers:

1. The long delay action current is set to 0.8 to 1 times the allowable current carrying capacity of the wire;

2. The return time of the motor of the 3 times long delay action current setting value is not less than the starting time of the motor with the maximum starting current in the line;

3. The short-delay action current setting value is not less than 1.1 (Ijx+1.35kIedm). Ijx calculates the load current for the line; k is the motor starting current multiple, and Iedm is the maximum rated current of one motor;

4. Short delay time according to the thermal stability check of the protected object;

5. When there is no short delay, the instantaneous current setting value is not less than 1.1 (Ijx+1.35k1kIedm). K1 is the impact coefficient of the motor starting current, which is 1.7 to 2.

If there is a short delay, the short-circuit current value is calculated at the input end of the lower-stage switch whose instantaneous current setting value is not less than 1.1.

Selection of automatic switch for motor protection:

1. Long delay current setting value = motor rated current;

2. The return time of 6 times long delay current setting value ≥ motor starting time;

3. The instantaneous setting current of the squirrel cage is 8-15 times of the rated current of the trip unit; the instantaneous setting current of the winding shape is 3-6 times the rated current of the trip unit.

Selection of automatic switch for lighting:

1. The long delay current setting value is not greater than the line calculation load current;

2. The instantaneous current setting value = 6 times the line calculates the load current.

Second, the selection of the knife switch

Protection: It is mainly used as an isolating switch. It does not cut off the fault current and can only withstand the electric power and thermal effects caused by the fault current.

Selection:

1. According to the rated voltage: the rated voltage of the knife switch ≥ the working voltage of the knife switch.

2. According to the rated current: the rated current of the knife switch ≥ the working current of the knife switch. If there is a motor in the circuit, the operating current should be calculated according to the motor starting current.

3. According to the thermal stability and dynamic stability check:

Imax ≥ ich. Imax: Maximum allowable current. Ich: Three-phase short-circuit inrush current.

Third, the fuse selection

Protection: Short circuit, if overload protection, the reliability is not high.

1, the choice of fuse melt

(1) Select according to normal working current

Melt rated current ≥ line calculation current

(2) Verify the sensitivity of the short-circuit current

Idmin/Ier≥Kr

Idmin: minimum short circuit current of the protected line

Kr: fuse action coefficient, generally 4

2, various types of equipment fuse selection

(1) Single motor circuit melt selection

Ier≥Iqd/α

Ier: melt rated current

Iqd: motor starting current

α: calculation coefficient, depending on the fuse characteristics of the starting condition

(2) Selection of distribution line melt

Iqd1: Starting current of the motor with the highest starting current in the line

Ig(n-1): line operating current other than the motor with the highest starting current

α: Calculated coefficient.

(3) Selection of lighting line melt

Ier≥Ig/αm

Ig: Line calculation current

Mm: calculation coefficient

(4) Selection of high and low pressure melts for transformers

1 Transformer with a capacity of 160KVA, its high-pressure melt is selected according to 2~3 times rated current; the transformer with capacity above 160KVA, high-pressure melt is selected according to 1.5~2 times rated current.

2 Transformer low-pressure melt is selected according to its rated current or 20% of overload current.

(5) Selection of electrostatic capacitor bank melt

Ier ≥ (1.5 ~ 2) Iec

Iec: rated current of the capacitor bank

3, the choice of fast fuse

Fast-acting fuses are mainly used for internal rectifier protection of silicon rectifier components, thyristor components and complete sets of devices.

(1) Small-capacity rectifier

Ier=1.57IF

Ier: The rated current of the fast fuse.

IF: thyristor forward average current

(2) Large capacity converter

m: number of parallel paths

Ki: dynamic current sharing coefficient, generally 0.5 to 0.6

Ar: Fuse maximum blow

Ak: Silicon component surge

Fourth, the selection of thermal relay

Protection: overload

1. Selection of long-term work or intermittent long-term work motor thermal relay

(1) Select according to motor starting time

Tf=(0.5~0.7)td

Tf: the return time of the thermal relay at 6Ie

Td: the operating time of the thermal relay at 6Ie

(2) Select according to the rated current of the motor

Iz=(0.95~1.05)Ied

Iz: Thermal relay setting current

Ied: rated motor current

(3) Select according to the requirements of phase failure protection

For the star-connected motor, a three-pole thermal relay can be used; for a delta-connected motor, a thermal relay with a phase-breaking operation protection device should be used.

Acer Adapter

High efficient charging speed for Acer laptop, stable current outlet can offer power for the laptop at the same time charge the laptop battery. The best choice for your replacement adapter. The DC connector is 5.5*1.7mm or 3.3*1.0mm. We can meet your specific requirement of the products, like label design. The plug type is US/UK/AU/EU. The material of this product is PC+ABS. All condition of our product is 100% brand new.

Our products built with input/output overvoltage protection, input/output overcurrent protection, over temperature protection, over power protection and short circuit protection. You can send more details of this product, so that we can offer best service to you!

Laptop Adapter For Acer,Charger For Acer,Acer Laptop Adapter ,Ac Adapter For Acer

Shenzhen Waweis Technology Co., Ltd. , https://www.waweispowerasdapter.com